QUOTATION DOCUMENT



Quotation number
W070100441
..




Description
:

Singo Road


Electrical Repairs


Works Order : 400329427


NOTES TO CONTRACTORS


The general conditions of this request for quota
tion are in accordance with
the

City of C
ape
T
own

s S
upply
C
hain
M
anagement
Po
licy.




1.

Q
uotations submitted by vendors not registered and verified on the
C
ity’s SAP

vendor database

may be
disqualified
.
Although the registration on the
Western Cape Supplie
r Database

(WCSD
) is not a
compulsory requirement by the
C
ity of
C
ape
T
own it will be beneficial for suppliers to register on this
database as well in order to claim preference points
(HDI

status)


2.

S
ite meeting:


A
compulsory

site meeting will be held for
all contractors to inspect and to ascertain the amount and
nature of work required prior to submitting their quotation where a project manager will be in attendance
on the date and site as detailed below
.
Note:

O
nly quotations submitted by contractors who
have
attended the compulsory site meeting will be considered for acceptance.
Council reserves the
right to extend the quotation date or postpone the site meeting.
V
endors arriving more that 15
minutes after the official site meeting time will not be allowed

to participate in the meeting
.


Date of site meeting

:

29
th

April 2010

Time



:

10:00

Venue



:

Gugulethu Electricity Depot


REQUEST FOR QUOTATION

(Under R30 000.00)



SUPPLY CHAIN MANAGEMENT

S
CM
-

532

Appr
oved

February 2010
:

B
ranch
M
anager

Version
1

Page
1

of
4


3.

Contact
details:





Proje
ct Manager: _______
Virgil Martin
__________________________________




Tel Number:
_____________
078 2477111
________________________________



4.

Each quotation must be submitted in a separate, clearly marked sealed envelope,
indicating the contents
(
description
) and the quotation box number
. It must be deposited in the relevant official nu
mbered
quotation box as specified by no later than the indicated closing date and time. Quotations will be opened
in public on the
closing

date as soon as possible after the closing time.


(
Cut
-
out

label

below and
paste

on your quotation envelope):



Atten
tion:
JP Groenewald

R
ef
:
W070100441

D
ue:


4 May 2010


Box No:
230 14h00


City of
C
ape
T
own. Tender
O
ffices.
8th


floor,
T
ower
B
lock
,

C
ivic
C
entre
,
12
Hertzog
B
oulevard, C
ape
T
own

































FORM OF OFFER





REFERENCE:


W070100441






Total Excluding Vat





R.........................


Add 14% VAT





R........................ Only if VAT
-
registered


TOTAL QUOTED PRICE




R…………………



COMPANY NAME:




CoCT Vendor
No:


Legal Address
(Domicillium citan
di et
executandi)




PHONE / CELL / FAX
:





TRADEWORLD REG
No:



IS YOUR COMPANY VAT
REGISTERED? *

Yes

No

Number of days from
receipt of official
purchase order to
commencement of
project









This done and signed at........................
..................................... on .....................................


For and on behalf of the contractor who by signature hereby warrants authorization.




Signature: ..............................................


Name (print).................
..........................


As Witness.............................................


Name (print)...........................................



























Specification:

LABELLING:

The following Items should be labeled:

Distribution boards
and circuit breakers
,
light switch points, plug socket outlets, geyser isolator points, fan points, air conditioner points, stove
points. All other fixed electrical equipment for example work shop machines, kwik hot geysers and test equipment.

The followin
g Information should be displayed on distribution boards:

The distribution board name and location

eg
. (ESS Main Office, Sub Board No. 1) The mains voltage, frequency and fault level at the main switch
(tested) as per SANS 10142. The name and location of t
he distribution board from where the sub board is fed. The circuit breaker number and
current rating feeding the specific sub board. The mains cable size and length. The circuits fed from the distribution board

indicating their purpose
and specific circui
t breaker number (legend card). The main switch must be identified and labeled as per SANS 10142.

The following Information should be displayed at the point of outlet:

The name of the distribution board feeding the specific circuit. (
DB1.1
/CB102) The circu
it breaker number feeding the specific circuit.
(
DB
1.1/
CB102
)

Label and legend card specification for distribution boards:

The label to be manufactured from double layered trefolite. The label ends to be machine beveled. The lettering to be mechani
cally en
graved. The
lettering to be in an Arial font sized to suite the label size. The lettering to be black on a white back ground. The labels
to be mounted in suitably
sized aluminium rail below the circuit breakers or below the point of outlet. The aluminium r
ail to be mounted with 3mm brass cheese head
machine screws equally spaced on both ends in distribution boards and with 8mm round head screws and fisher plugs equally spa
ced on both
ends or in an alternative but approved manner at points of outlet. The leg
end card should display all the circuit breaker numbers and the purpose
of the circuits. The legend card should be in a printed format with Arial font, sized to suit the card holder. The legend car
d holder should be of a
metal type with a transparent cover
. The holder should be mounted adjacent to the distribution board with 6mm round head brass screws and
fisher plugs, two at the bottom and one on top, should the distribution board not have a legend card mounting facility. The s
crews should be
mounted thro
ugh the legend card and transparent cover in order to prevent the card from being removed.

Documentation:

The distribution system should be drawn in a single line diagram format with a cad package on an A4 page, indicating the foll
owing information.

The
distribution board names. The fault level at the main switches (tested). The location of the distribution boards. The circuit

breaker number and
current rating feeding the specific sub board. The cable sizes and lengths. The distribution board legend card
s should be attached to the layout
diagram. The documents should be provided in triplicate in a document binder format.

CONDUIT:

PVC: 20mm, 25mm or 32mm PVC SABS conduit may be used. Conduit will be mounted with PVC spacer bar saddles, spaced not more t
han
600mm apa
rt. Saddles to be mounted with 6
mm
(in size or higher)

fisher plugs and suitably sized brass counter sunk screws on brick or concrete
walls. Saddles to be mounted with 5 x 10mm counter sunk galvanised steel screws on steel beams.
Saddles to be
mounted with 6 x 16mm dry
wall screws
on
wood ceiling or

beams. Inspection points should be provided after each 180 degree bend.

BOSAL: 20mm, 25mm or 32mm BOSAL conduit may be used. Conduit will be mounted with galvanised spacer bar saddles, spaced not m
or
e than
1500mm apa
rt. Saddles to be mounted with 6
mm
(in size or higher)

fisher plugs and suitably sized brass counter sunk screws on brick or concrete
walls. Saddles to be mounted with 5 x 10mm counter sunk galvanised steel screws on steel beams. Conduit mu
st be re
-
wire able. Inspection
points should be provided after each 180 degree bend. Grey PVC end caps should be fitted on all open conduit ends.

TELEMETRY SUPPLY POINT:

All units will be supplied via a 32Amp, 2 pole, pad lockable isolator that is surface
mounted, enclosed to IP65 and mounted next to the telemetry
panel (RTU). The isolator shall be supplied from a 20 Amp, circuit breaker with 2.5mm, 2 core, black, surfix cable or with 2.
5mm house wire
sleeved in 20mm pvc conduit should the isolator be situa
ted in close proximity to the distribution board. Cable entries into isolators will be via steel
compression glands through the bottom or the rear of the isolator and panel. The surfix cable shall be sleeved into PVC condu
it. The contractor
shall also repl
ace the equipment’s supply cable as per above. Please note that this equipment may not be left un powered for more that 1 hou
r.

BULKHEAD FITTINGS:

Energy saving bulkhead light fittings will be
BEKABULKHEAD 1 x 18W CFL 31118

or similar to be approved

Energ
y saving bulkhead light fittings will be
BEKANOVA 4X26w CFL / DS / IE / PV

or similar to be approved

Energy saving bulkhead light fittings will be BEKABULK, 2 x 9Watt CFL or similar to be approved.

Energy saving bulkhead light fittings will be BEKABULK, 2
x 18Watt CFL or similar to be approved.

Emergency

bulkhead li
ght fittings will be BEKABULK, 1

x 18Watt CFL or similar to be approved.

Bulkhead light fittings will be BEKANOVA, 250Watt MV
,

BE, DS, IE, PV
or similar to be approved.

Bulkhead light fittings wi
ll be BEKANOVA,
125
Watt MV
, BE, DS, IE, PV or similar to be approved.

Bulkhead light fittings will be
BEKANOVA, WG, 2 x 26 Watt CFL or similar to be approved.

Bulkhead light fittings will be BEKA Series 70, CFL or similar to be approved.

Mounting:

Bulkhead

fittings to be mounted with 8mm couch bolts, washers and suitably sized fisher plugs on brick or concrete walls. Rear entry i
nto bulkhead
fittings will be preferred.

FLOOD LIGHT FITTINGS:

Energy saving flood light fittings will be ACDC, GX85306, 2 x 18Wa
tt, PLC
-
18 Lamp, 0.375A, IP65, 2.7kg or similar to be approved.

Energy saving flood light fittings will be ACDC, GX85307, 2 x 26Watt, PLC
-
26 Lamp, 0.4A, IP65, 2.7kg or similar to be approved.

Energy saving flood light fittings will be ACDC, GX85066, 2 x 42
Watt, PLCE
-
42 Lamp, 0.45A, IP65, 5.2kg or similar to be approved.

Floodlight fittings will be BEKAMAX
-
F 400W MH
-
T WB, HQI
-
T 400W lamp, grey with stirrup for wall mounting or similar to be approved.

Floodlight fittings will be
BEKAMAX ,120 Watt CFL, with wi
re guard,

grey with stirrup for wall mounting or similar to be approved.

Floodlight fittings will be BEKABEAM 400W MH
-
T WB, HQI
-
T 400W lamp, with stirrup for wall mounting or similar to be approved.

Floodlight fittings will be BEKABEAM 400W HPS
-
T WB, HQI
-
T

400W lamp, with stirrup for wall/pole mounting or similar to be approved.

Floodlight poles will be 9 meter concrete with a 76mm diameter spigot.

Floodlight pole mounting bracket will be BEKA, Double Floodlight Mounting H.D.G. as per drawing No. PDP
-
021
-
00
2 or similar to be approved.

Mounting:

Floodlight fittings to be mounted with 10mm couch bolts, washers and suitably sized fisher plugs on brick or concrete walls.
Floodlight fittings will
also be supplied via surface joint boxes, CCG No. 0, 4 way, grey or

similar to be approved. Cabling to flood lights will be done with 2.5mm, 2 core,
black, surfix cable, sleeved into 20mm PVC SABS conduit, mounted with 20mm PVC spacer bar saddles, spaced 500mm apart. Saddle
s to be
mounted with 8mm fisher plugs and suitabl
y sized brass counter sunk screws on walls. Saddles to be mounted with 5 x 10mm counter sunk
galvanised steel screws on steel beams. The surfix cable should be glanded with Pratley, steel, compression gland or similar
to be approved. Pole
mounted floodligh
t fittings to be mounted with suitably sized 10mm stainless steel bolts, nuts and washers to hold the stirrup tightly clamped

to the
pole mounting.

FLUORESCENT LIGHT FITTINGS

FOR GENERAL, SUB STATION AND OUTDOOR APPLICATIONS
:

Nordland, JB265, IP65, 5 foot
, double fluorescent fittings will be installed into all outdoo
r or moist environments.
All light fittings will be SABS
approved. Fluorescent fittings to be mounted with 8mm fisher plugs and suitably sized brass counter sunk screws with 6 x 30mm

penny wash
er on
concrete or brick walls.

Fluorescent fittings to be mounted with 5 x 20mm galvanised steel, cheese head screws and 5mm x 30mm penny
washers, drilled and tapped on a steel structure.

Fluorescent fittings to be mounted with 5 x 37mm met
al cavity anchor
s

on dry walls or rhino board
ceilings. Fluoresce
nt fittings to be mounted with 6 x 16mm drywall screws and 6 x 25mm penny washers onto wooden beams or

ceilings. A
minimum of two fixtures per fitting is required.

PHOTOCELLS:

Photocells will be enclosed, a
nd surface mounted. Photocells will be able to be replaced without disconnecting any wiring. Photocells will be
mounted in such a way that they are only affected by sunlight. Fitting of light reflecting covers for photocells will not be
permitted. Photocel
ls will be
surface mounted with 4 x 6mm fisher plugs and suitably sized brass counter sunk screws. Photocells will be Spectrum QS15 or s
imilar to be
approved.

LIGHT SWITCHES:

Switches will be 16Amp, Crabtree. Push button type switches will be fitted for d
immable lights. All switches will be fitted with PVC cover plates and
4mm
steel counter sunk screws
. Switches will be flush mounted unless other wise specified. Surface mounted switches will be fitted with 2 x 4 or 4
x 4 PVC surface boxes. Flush mounted sw
itches will be supplied via 25mm conduit. Conduits to surface and flush boxes will be fitted with male
adaptors and lock nuts. Outdoor light switches will be 16Amp, 2 pole, pad lockable isolators that is surface mounted, enclose
d to IP65.

PLUG SOCKET OUTL
ETS:

Socket outlets will be 16Amp double, Crabtree. Socket outlets in sub stations will be 13Amp

or 16Amp

single, Crabtree. All socket outlets will be
fitted with PVC cover plates and 4mm steel counter sunk screws. Socket outlets will be flush mounted unle
ss other wise specified. Surface
mounted socket outlets will be fitted with 4 x 4 PVC surface boxes. Conduits to surface and flush boxes will be fitted with m
ale adaptors and lock
nuts. All plug socket outlets in power skirting or connected via conduit wi
ll be wired with 2.5mm house wire.

DISTRIBUTION BOARDS:

Distribution boards shall be manufactured with “CNC” type bending and cutting equipment. Distribution boards shall be
of a
modular

construction.
Distribution boards shall be type tested, labelled and

certified as per SANS 10142
. A minimum of 1.6mm sheet metal will be used for the
construction.

Distribution boards shall be powder coated, electrical panel orange
.
The colour will be confirmed on order.
Dedicated or standby
power distribution board shall
be red in colour. The distribution board shall cater for specified circuit breakers and 30% free space for future
expansion. The main switch will be in a separate compartment with a separate door and cover on the left hand side of the dist
ribution board.
C
ircuit breaker covers will be of similar construction as the distribution board, to be hook and screw down type. Circuit brea
kers shall be fitted onto
cradles and be of the Samite or DIN type as approved Mounting rails. Doors will be hinged with Perano pad

lockable handle. The distribution board
shall be fitted with engraved numbering below the circuit breakers. The spacing will align with the circuit breakers installe
d black on white, bevelled
edges, mounted with 3mm round head brass screws. The board will

also be fitted with an engraved name on the top centre on the outside of the
distribution board frame. Labels shall have bevelled edges, black on white, mounted with 3mm round head brass screws tapped i
nto board. A
metal welded legend card holder on shall

be fitted on the inside of the door with a printed legend card indicating the circuit information linked to the
circuit breaker number. 2 x square mounting brackets on top and bottom of the board shall be provided. Board to be mounted wi
th suitably sized
couch bolts, washers and suitably sized fisher plugs on brick or concrete walls. Circuit breakers will be CBI, Samite, 6kA, 1
3mm frame sizes or as
approved. CBI, black, clip into samite rail, blank units will be provided in each open circuit breaker space.

The use of door clip units will not be
allowed. The main switch will feed suitably sized copper bus bars, mounted on insulators above the main switch. Only screw do
wn type terminals
will be allowed on all bus bars. No lug type terminals will be allowed. S
uitably rated copper circuit breaker mounted bus bars should be used and
bridge pieces made of wire should be limited as far as possible. Wiring should be colour coded, suitable rated and only house

wire should be used.
No taping or heat shrink colouring
will be allowed.

PANELS:

Panels will be wired with 1mm copper, panel wire or as required to suitably cater for current carrying capacity and fault lev
els. All panel wire shall
be suitably protected against over load and fault levels. All panel wire shall
be sleeved into grey slotted trunking. All panel wire looms shall be
sleeved in black wire sock, wire socks shall be clamped close at ends with black cable ties. All wire ends to be terminated v
ia suitably sized
bootlace ferrules. All wire ends to be marke
d with suitably sized wire numbers that should also be colour coded. Joints may only be done via din
terminals. All terminals shall be 4mm. All terminals shall be fitted with end caps and end stops. All wiring to be as per the

equipment
manufacturer’s reco
mmendations. All wiring to be documented with a CAD type program. CAD drawings to be provided for approval before
manufacturing. As built CAD drawings to be supplied on completion. All bus bars shall be suitably sized and rated according t
o the expected fa
ult
levels. All nuts and bolts shall be new and of the same shape and size. No bolts may be cut to alter lengths. All bolts, nuts

and washers shall be
electro galvanised. All connections shall be tightened to the required torque as per the manufacturer’s s
pecifications. All auxiliary equipment
required to finish off panels, doors, cuttings etc. shall be installed as per the manufacturer’s specifications. All sheet me
tal work shall be pre
-
manufactured and powder coated. All equipment shall be pre
-
tested and
witnessed by the project manager prior to installation.

BATTERY CHARGER SUPPLY POINT:

All units will be supplied via a 32Amp, 2 pole, pad lockable isolator that is surface mounted, enclosed to IP65 and mounted n
ext to the battery
charger panel. Th
e isolator shall be supplied from a 20 Amp, circuit breaker with 2.5mm, 2 core, black, surfix cable or with 2.5mm house wire
sleeved in 20mm pvc conduit should the isolator be situated in close proximity to the distribution board. Cable entries into
isolat
ors will be via steel
compression glands through the bottom or the rear of the isolator and side of the charger panel. The surfix cable shall be sl
eeved into PVC
conduit. The contractor shall also replace the equipment’s supply cable as per above. Please n
ote that this equipment may not be left un powered
for more that 1 hour.

LABELLING:

The following Items should be labeled:

Distribution boards and circuit breakers
,
light switch points, plug socket outlets, geyser isolator points, fan points, air conditi
oner points, stove
points. All other fixed electrical equipment for example work shop machines, kwik hot geysers and test equipment.

The following Information should be displayed on distribution boards:

The distribution board name and location. The mains v
oltage, frequency and fault level at the main switch (tested) as per SANS 10142. The name
and location of the distribution board from where the sub board is fed. The circuit breaker number and current rating feeding

the specific sub
board. The mains cable
size and length. The circuits fed from the distribution board indicating their purpose and specific circuit breaker number
(legend card). The main switch must be identified and labeled as per SANS 10142.

The following Information should be displayed at th
e point of outlet:

The name of the distribution board feeding the specific circuit. The circuit breaker number feeding the specific circuit.

Label and legend card specification for distribution boards:

The label to be manufactured from double layered tref
olite. The label ends to be machine beveled. The lettering to be mechanically engraved. The
lettering to be in an Arial font sized to suite the label size. The lettering to be black on a white back ground. The labels
to be mounted in suitably
sized alumini
um rail below the circuit breakers or below the point of outlet. The aluminium rail to be mounted with 3mm brass cheese head
machine screws equally spaced on both ends in distribution boards and with 8mm round head screws and fisher plugs equally spa
ced on

both
ends or in an alternative but approved manner at points of outlet. The legend card should display all the circuit breaker num
bers and the purpose
of the circuits. The legend card should be in a printed format with Arial font, sized to suit the card h
older. The legend card holder should be of a
metal type with a transparent cover. The holder should be mounted adjacent to the distribution board with 6mm round head bras
s screws and
fisher plugs, two at the bottom and one on top, should the distribution b
oard not have a legend card mounting facility. The screws should be
mounted through the legend card and transparent cover in order to prevent the card from being removed.

Documentation:

The distribution system should be drawn in a single line diagram form
at with a cad package on an A4 page, indicating the following information.

The distribution board names. The fault level at the main switches (tested). The location of the distribution boards. The cir
cuit breaker number and
current rating feeding the spec
ific sub board. The cable sizes and lengths. The distribution board legend cards should be attached to the layout
diagram. The documents should be provided in triplicate in a document binder format.

ALARM CHARGER SUPPLY POINT:

All units will be supplie
d via a 16Amp, double, dedicated plug socket outlet. The plug socket outlet will be mounted into a York U7 slide lid
enclosure with wooden mounting board. The dedicated plug socket outlet shall be supplied from a 20 Amp, circuit breaker with
2.5mm, 2 core,

black, surfix cable or with 2.5mm house wire sleeved in 20mm pvc conduit should the isolator be situated in close proximity t
o the distribution
board. Cable entry into the enclosure will be via steel compression glands through the bottom of the enclosure.

The surfix cable shall be sleeved
into PVC conduit. The alarm system power supply will be mounted next to the plug socket outlet in the York enclosure. The pow
er supply will be
plugged into the one outlet and the low voltage DC supply will be extended to
the alarm system control unit. Please note that this equipment may
not be left un powered for more that 1 hour.

ALARM CHARGER SUPPLY POINT:

All units will be supplied via a 16Amp, double, dedicated plug socket outlet. The plug socket outlet will be mounte
d into a York U7 slide lid
enclosure with wooden mounting board. The dedicated plug socket outlet shall be supplied from a 20 Amp, circuit breaker with
2.5mm, 2 core,
black, surfix cable or with 2.5mm house wire sleeved in 20mm pvc conduit should the isola
tor be situated in close proximity to the distribution
board. Cable entry into the enclosure will be via steel compression glands through the bottom of the enclosure. The surfix ca
ble shall be sleeved
into PVC conduit. The alarm system power supply will be

mounted next to the plug socket outlet in the York enclosure. The power supply will be
plugged into the one outlet and the low voltage DC supply will be extended to the alarm system control unit. Please note that

this equipment may
not be left un powered
for more that 1 hour.



*

NOTES FOR ALL SUBSTATON UPGRADES





SUPPLY FROM THE KIOSK, POLE OR THE LOCAL TRANSFORMER:

Note: Please delete which is not applicable and amend quantities as per the site
meeting instructions.

Each





Install a 40Amp slow c
urve

supply circuit breaker

in the kiosk, DB or on the pole.


Each


1



Install meters 16mm x 2core SWA, copper cable with 16mm green copper earth
cable or 10mm 2 core black Surfix cable from the supply point to a York J7 junction
box through a Bosal slee
ve installed as per the specification.

Each


1



Install a York J7 junction box with earth/neutral bar, mounted surface inside the sub
station next to the distribution board.

Each


1



Install meters 16mm x 2 core SWA copper cable or house wire and 16mm

green
earth cable from the York J7 junction box to the distribution board, cable sleeved into
25mm bosal or PVC conduit.

Each


1



Earth spikes with 10mm green house wire sleeved into 20mm pvc conduit to York J7
junction box earth/neutral bar. 20 ohm ear
th spike reading to be obtained.

Each


1







Project Scope/Price schedule: Singo Road S/Station



Work
s Order 400329427

Item

D E S C R I P T I O N

Unit

Quantity

Price


Isolate and remove existing distribution board, redundant circuits, cabling, conduits
wire ways, labelling etc.



1



Supply a cad proposal and single line diagram of the new dis
tribution boards and
mains cabling.



1



MAIN DISTRIBUTION BOARD





Fit and supply blanks for distribution board as to be discussed on site. All circuit
breaker blanks to be of the correct standard and size.



1



Fit and supply a legend for
the distribution board



1








EARTHING





A separate earth conductor of greater or equal to 16mm will be used as the supply
earth conductor for the Distribution Board. A earth resistance reading must be
obtained as specified in SANS10142
-
1



1



All extraneous conductive equipment as well as all electrical equipment will be
connected to the electrical supply earth bar from the Distribution Board with a
conductor as per SANS 10142
-
1 code.



1








INTERIOR LIGHTING IN SWITCH GEAR AND TRANSFORME
R ROOM:





Nordland JB265, 5 foot double, surface fluorescent fittings. The new fittings will be
wall or ceiling mounted. This will be confirmed during the site meeting:

Walls……………….

Ceilings……………..

(note: please mark which method will be applicable)







5



Switch point, surface or flush, single lever.




1



Replace lighting circuit and conduits with new.




1



Install SANS10142
-
1 dome cover type fitting in toilet




1



EXTERIOR LIGHTING:







Test to see if exteri
or lighting is operating correctly from the photocell. Repair any
faults found on the exterior lighting circuits. If the light fittings or the photocell needs
to be change the correctly selected fittings should be used as per specifications





1



Install one single lever light switch next to the substation entrance door to act as an
override for the photocell of the exterior lightning.





1









PLUGS






Install double, 16Amp, 3 pin plugs as per required. All plug socket outle
ts to be of
SANS 10142
-
1 standard and must be mounted in a proper and neat manner. Where
indicated a plug socket outlet will be changed from an existing flat pin plug type to
the standard domestic plug socket outlet type as per required.




1








BATTERY CHARGER:





Install new lockable isolator for battery charger as per specifications





1








ALARM CHARGER SUPPLY POINT:






Install and supply alarm power point as per specifications





1








LABELLING:





Label above circuits as per specification. Samples in brackets.





1








CERTIFICATION
:





Perform an electrical compliance inspection and issue a Certificate of Compliance.



1








SAFETY:






A safety plan to be compiled
and to be handed in with this quotation document.





1



Implement a site safety file and plan.




1





NOTE:

1.

The safety specification can be down loaded from the following web
site:http://www.capetown.gov.za/en/SupplyChainManagement/Page
s/
RequestforQuote.aspx

2.

ESS will employ a safety consultant in order to manage all the site
safety aspects pertaining to this project.

3.

Contractors must have completed the ORHVS regulations modules 1,2,3,4, and
7 so that a


permit can be issued to t
he supervisor of the work.






TOTAL PRICE CARRIED TO FORM OFFER