DIGITAL SYNCHRONIZING SYSTEM

SOLICITATION R10PS17367

SPECIFICATIONS

The Bureau of Reclamation, Grand Coulee Power Office, Grand Coulee WA, has a requirement for

46
Beckwith Synchrocloser Check Relays, and

32
Beckwith M
-
5625 Digital Synchronizing Systems an
d
comprises a digital auto
-
synchronizer. Each of these systems must consist of an M
-
3410A Intertie/Generator
Protection Relay, an M
-
0193B Syncrocloser Unit, and an M
-
0194 Generator Control Unit, per the following
specifications:

CLIN 1:
SYNCROCLOSER

CHECK
RELAY


UNIT DESCRIPTION:

The M
-
0188A Syncrocloser® Check Relay is used as a permissive relay for secure
reclosing of a circuit breaker by verifying that voltage and phase angle conditions are within pre
-
set limits
before allowing the breaker to close. Adju
stable front panel controls are provided for upper and lower voltage
limits, voltage di
fference (ΔV) limit, phase angle limit, time delay and dead line/bus limits. Analog outputs of
phase angle, voltage and ΔV are provided for SCADA system interface. Phase angle, voltage and time delay
dial settings are independent and do not vary with input

conditions.

Base Unit:

Timer Logic: Start Timer = Phase Angle OK
AND
Enable Sync
-
Check (M2
-
S)

Phase Angle Limit: 30 degrees (E1
-
S)

Time Limit (SEC.): 15 sec (G2)

Phase Angle Reduction Ratio: 1/2 (H1
-
S)

Time Reduction Ratio: 1/2 (I1
-
S)

Phase angle analog
Output: 0 to 1.0 mA = 0 to 180 degrees (Q2
-
S)

Voltage Package:

Delta V Limit: 2 to 10 V ac (B2)

Bus Voltage Analog output: 0 to 1.0 mA = 0 to 150 V ac (N2
-
S)

Line Voltage Analog Output: 0 to 1.0 mA = 0 to 150 V ac (O2
-
S)

Delta Voltage Analog Output: 0 to 1

mA = 0 to 20 V ac (P2
-
S)

Timer Logic: Start Timer = Voltage OK AND Phase Angle OK AND Enable Sync
-
Check (M4
-
S)

Operator Frequency: 60Hz (L2
-
S)

Mounting/Language: Hortizontal/English (R1
-
S)

Accessory: NA


BECKWITH ELECTRIC MODEL M
-
0188A

WARRANTY: ________
________________


CLIN
2
:

The M
-
5625 Syncrocloser Digital Synchronizing System is suitable for the automatic synchronizing of
a generator to the electric power network. The system provides speed and voltage “jogs” to bring a generator to
proper conditions
of matching voltage and frequency, prior to safely and accurately closing a breaker into a bus
energized by an electric power network. The Digital Synchronizing System is intended for three general classes
of application:



Initial connec
tion of a generator
to a power
n
e
twork



Closure of a network breaker where there is a possibility of a split of the system into two isolated
networks having different frequencies



Breaker closure applications with a static phase angle

To include:

SYNCROCLOSER UNIT


M
-
0193B

The

M
-
1093B Syncrocloser Unit closes the generator breaker at the point of synchronism. It initiates the close
command n advance of phase coincidence using breaker closing time and slip frequency, accurate to +/
-

.05
degree at slip frequencies below 0.1 Hz. A
djustable front panel controls are provided for upper and lower
voltage, voltage difference limit and frequency difference limit. Gen/line, bus and supply voltages are
transformer isolated to allow freedom in application. The M
-
0193B includes the M
-
1094 Ge
nerator Control
Unit compatibility feature, and the user
-
selectable anti
-
motoring feature.

1. Delta Voltage Limit


2 to 10 V ac

2. Delta Frequency Limit
-

.05 to .5 Hz

3. Anti
-
Pump Feature

4. Operator Frequency


60 Hz

GENERATOR CONTROL UNIT


M
-
0194

T
he M
-
0194 Generator Control Unit matches the generator speed and voltage to system conditions in minimum
time with output control jogs that use a proportional pulse width algorithm. The time between jogs is adjustable
to match the response characteristics
of the control, prime mover and generator system. The kicker pulse brings
phase angle around through zero degrees if speed is matched but synchronism has not yet occurred.

M
-
0194 Options:

1. Speed Matching


2 to 30 Seconds

2. Voltage Matching


2 to 30 S
econds

3. Operator Frequency


60 Hz


INTERTIE/GENERATOR PROTECTION


M
-
3410A

The Intertie/Generator Protection System M
-
3410A provides protection, control, and monitoring and user
interface functions. It includes protection for abnormal voltage, frequen
cy, overcurrent, directional power, and
VT fuse loss. Sync
-
check and programmable reconnect time are also provided. Stored sequence of events and
oscillography are included as extended functions. RS
-
232 and RS
-
485 communication ports provide user and
SCADA

interface capabilities. The M
-
3810A IPScom Communications Software is included for direct serial or
remote communications access. Waveform data can be downloaded using IPScom while the IPSplot PLUS
Oscillograph Analysis Software allows for plotting and pr
inting of the downloaded oscillographic data. Sensing
voltage up to 480 volts, accepts 1 A or 5 A nominal current, phase rotation
(
ABC or ACB) and nominal
frequency (50 or 60 Hz) are user selectable in software.

Intertie/Generator Protection M
-
3410A includ
es IPScom software and the following protective functions:



Sync Check



Phase undervoltage and overvoltage protection



Directional power protection



Dual
-
setpoint negative sequence overvoltage protection



Three
-
phase inverse time overcurrent protection with voltage control/voltage restraint



VT fuse
-
loss detection and blocking



Reconnect enable time function



Four
-
step over/underfrequency protection

M
-
3410A Options

1. Power Input Options


125 V dc or 120 V ac

Nominal

2. Output Contact Options


Two Form A Contacts

BECKWITH ELECTRIC MODEL M
-
5625.

WARRANTY: _____________________________